EN 61000-3-11, “Electromagnetic compatibility (EMC) – Part 3-11: Limits – Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems – Equipment with rated current ≤ 75 A and subject to conditional connection”, applies the flicker limits to equipment above 16 A and to equipment that fails the limits with the reference impedance. It is the continuation of EN 61000-3-3 and belongs to the low-frequency emission side of EMC testing.

Let us take care of EN 61000-3-11 assessment and the CE marking of your product together; CE Danışmanı (CE Consultant) manages the whole process.

EN 61000-3-11 harmonised standard

What is this standard for?

A product drawing a large current can cause enough voltage drop at start-up to make lamps blink. The size of the drop depends not only on the product but also on the impedance of the network it is connected to: a product that causes no trouble in a strong installation exceeds the limit on a weak line. EN 61000-3-11 solves this with “conditional connection”: the product is deemed compliant on condition that it is connected only to networks of a certain quality, and the manufacturer tells the user what that condition is.

The flicker criteria and the measurement method are the same as in EN 61000-3-3; what changes is the impedance at which the product is assessed and how the result is declared.

EN 61000-3-11 at a glance

Current editionEN IEC 61000-3-11:2019 (IEC 61000-3-11:2017); replaces EN 61000-3-11:2000
Official titleElectromagnetic compatibility (EMC) – Part 3-11: Limits – Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems – Equipment with rated current ≤ 75 A and subject to conditional connection
Type of standardMains emission standard: it defines the assessment route and the declaration conditions; the limits come from EN 61000-3-3
LegislationEMC Directive 2014/30/EU; the generic emission standard EN 61000-6-3 refers to it for flicker

Which products does it apply to?

Equipment connected to the public low-voltage network (220-250 V line to neutral, 50 Hz) with a rated current above 16 A and up to 75 A per phase. Two further cases fall under this standard:

  • Equipment within the scope of EN 61000-3-3 (≤ 16 A) that fails the limits when measured with the reference impedance may be assessed here by way of conditional connection.
  • Equipment above 16 A that meets the EN 61000-3-3 limits with the reference impedance is not subject to conditional connection; the manufacturer may declare this in the documentation.
  • Typical products: large air conditioners and heat pumps, industrial compressors, welding equipment, commercial kitchen appliances, electric vehicle charging units.

Assessment flow

EN 61000-3-11 conditional connection assessment flow (schematic)

  1. Measurement: the equipment is measured with the EN 61000-3-3 circuit; Pst, Plt, dc, dmax and Tmax are recorded.
  2. Test impedance: for high-current equipment a lower test impedance may replace the reference impedance. The conditions are that the steady-state voltage drop stays between 2 % and 9 % of the test voltage and that the X/R ratio of the impedance lies between 0.5 and 0.75.
  3. Converting the results: if the test impedance differs from the reference impedance, the measured values are multiplied by the ratio of the two impedances to obtain their reference-impedance equivalents.
  4. Decision: if the values meet the EN 61000-3-3 limits, the equipment is connected without conditions. If not, it is subject to conditional connection and the manufacturer chooses one of two routes.
  5. Route a, Zmax declaration: the maximum system impedance at which the equipment still meets the limits is calculated and stated in the instruction manual; the user, consulting the supply authority if necessary, checks that the impedance at the point of connection is below this value.
  6. Route b, 100 A service capacity: the equipment is assessed with the additional test in the standard and the manual states that it is intended only for premises with a service current capacity of 100 A or more per phase on a 400/230 V network; the equipment is marked accordingly.

Limits

QuantityLimitNote
Pst≤ 1.0short-term severity over 10 minutes
Plt≤ 0.65long-term severity over 2 hours
dc≤ 3.3 %relative steady-state voltage change
dmax4 % / 6 % / 7 %depending on how the equipment is switched and restarted
Tmax≤ 500 mstotal time d(t) exceeds 3.3 %

The limits are the same as in EN 61000-3-3; conditional connection does not relax them, it only changes the network impedance at which the assessment is made.

How is compliance assessed?

  • The result takes one of three forms: compliant without conditions, compliant with a Zmax declaration, or compliant subject to a 100 A service capacity.
  • Under conditional connection the declaration and the user information are part of compliance; without the relevant sentence in the manual the assessment is incomplete.
  • Under route a, the supply authority may restrict use if the actual impedance at the point of connection exceeds Zmax.

Place in the CE marking process

  1. The rated current of the equipment is determined; unconditional compliance with EN 61000-3-3 is tried first.
  2. If the limits are exceeded, soft starting or staged starting is reviewed during design; the conditional connection route is chosen for the remaining difference.
  3. The measurement is carried out in an accredited laboratory; the report records the test impedance, the conversion factor and the declaration route chosen.
  4. The report goes into the technical file; the manual and marking are prepared; the EU Declaration of Conformity under the EMC Directive is drawn up and the product is CE marked.

Standards applied together

  • EN 61000-3-3: flicker limits and measurement method for equipment up to 16 A
  • EN 61000-3-12: harmonic current limits for equipment above 16 A
  • EN 61000-6-3 and EN 61000-6-4: generic emission for residential and industrial environments

Frequently asked questions

Does conditional connection prevent the product from being sold?

No. The product is placed on the market with the CE marking; the difference is that the user is informed of the connection condition. The Zmax value or the 100 A service capacity notice in the manual tells the user which installations the product is suitable for.

How is Zmax determined?

The measured voltage changes and flicker values of the equipment are scaled up to the impedance at which the limits are just met; that value is Zmax. The standard defines how the calculation is made and how it is expressed in the manual.

Does every product above 16 A fall under this standard?

No. Equipment above 16 A that meets the EN 61000-3-3 limits with the reference impedance is not subject to conditional connection and the manufacturer may declare this. EN 61000-3-11 is only for equipment that cannot meet the limits or is designed for conditional connection from the start.

Other standards in this group

All standard guides

Our EMC test requirements tool shows which EMC tests your product needs in a few questions.

Get an offer for your product

Scope, timeline and price in three steps.

  1. 1Tell us about your productAttach a datasheet or photos if you have them
  2. 2Scope and tests become clearDirectives, tests, notified body
  3. 3Price and timeline in your handsOffer within one business day

Prefer to talk now?

Leave your details

Reply within one business day

By sending this form you agree that your data is processed as described in our Privacy & Cookie Policy.